1.0 -> 1.1
* Operation changes:
The boiler now operates from its requested temperature to +hysteresis, instead of oscillating at +/- hysteresis/2.
This means that the heat circuit and DHWT "temp_inoffset" can be set being assured that the boiler will
attempt to maintain a temperature strictly above the requested input temperature.
In other words, there is no longer a need to account for the boiler's own hysteresis in setting these values.
Example with DHWT: target DHWT temp: 60C. DHWT "temp_inoffset" set at 5C;
Old behaviour: boiler trips at 65C-hysteresis/2 and untrips at 65C+hysteresis/2
New behaviour: boiler trips at 65C and untrips at 65C+hysteresis: DHWT always gets input >=65C
For DHWT, "t_legionella" no longer overrides t_min/t_max and must thus be set within those two values.
* Configuration changes:
- Renamed options:
- DHWT:
- "valve_hwisol" -> "valve_feedisol"
- "pump_recycle" -> "pump_dhwrecycle"
- Added options:
- Defconfig:
- "notifier": string path to an executable that will be called when an alarm is raised in the system
- Pump:
- "shared": boolean, signals a pump shared between several plant entities
- DHWT:
- "electric_hasthermostat": boolean, if true, DHWT has its own thermostat for electric operation.
- "tthresh_dhwisol": minimum temperature threshold for DHWT disconnection from DHW circuit
- Hcircuit params:
- "inoff_temp": maximum indoor temperature for circuit operation
- Removed options:
- Pump:
- "cooldown_time": no longer necessary (logic handled at entity level)
- Boiler:
- "pump_load": removed untested implementation
- DHWT:
- "electric_failover": superseeded by "electric_hasthermostat"
- Modified options:
- Hcircuit:
- "fast_cooldown": now a list of allowed modes for fast cooldown operation